Blog
Understanding Time Delay Relay Functions
Monday, October 3, 2022
Understanding Time Delay Relay Functions
Issue:
What is the difference between On Delay, Off Delay, Single Shot, Interval On and all these other time delay functions?
Solution/Resolution:
Understanding the differences between all the functions available in time delay relays can sometimes be a daunting task. When designing circuits using time delay relays, questions such as what initiates a time delay relay, does the timing start with the application or release of voltage, when is the output relay energized, etc., must be asked.
Time delay relays are simply control relays with a time delay built in. Their purpose is to control an event based on time. The difference between relays and time delay relays is when the output contacts open & close: on a control relay, it happens when voltage is applied and removed from the coil; on time delay relays, the contacts can open or close before or after some time delay.
Typically, time delay relays are initiated or triggered by one of two methods: application of input voltage
opening or closing of a trigger signal
These trigger signals can be one of two designs: a control switch (dry contact), i.e., limit switch, push button, float switch, etc. voltage (commonly known as a power trigger)CAUTION: any time delay relay that is designed to be initiated with a dry contact control switch trigger could be damaged if voltage is applied to the trigger switch terminals. Only products that have a "power trigger" should be used with voltage as the trigger.
To help understand, some definitions are important:
Input Voltage-control voltage applied to the input terminals. Depending on the function, input voltage will either initiate the unit or make it ready to initiate when a trigger is applied.
Trigger Signal-on certain timing functions, a trigger is used to initiate the unit after input voltage has been applied. As noted above, this trigger can either be a control switch (dry contact switch) or a power trigger (voltage).Output (Load)-every time delay relay has an output (either mechanical relay or solid state) that will open & close to control the load. Note that the user must provide the voltage to power the load being switched by the output contacts of the time delay relay.
Below are both written and visual descriptions on how the common timing functions operate. A Timing Chart shows the relationship between Input Voltage, Trigger (if present) and Output. If you cannot find a product to fit your requirements or have any questions,
NOTE: Not all functions are available on any of our multi-function products. Please check the catalog pages or specification sheets of each multi-function product to confirm what functions are included.
ON DELAY
Delay on Make Delay on Operate
Upon application of input voltage, the time delay (t) begins. At the end of the time delay (t), the output is energized. Input voltage must be removed to reset the time delay relay & de-energize the output.
INTERVAL ON Interval Upon application of input voltage, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Input voltage must be removed to reset the time delay relay.
OFF DELAY Delay on Release Delay on Break Delay on De-Energization Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output is energized. Upon removal of the trigger, the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Any application of the trigger during the time delay will reset the time delay (t) and the output remains energized. SINGLE SHOT One Shot Momentary Interval Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output is energized and the time delay (t) begins. During the time delay (t), the trigger is ignored. At the end of the time delay (t), the output is de-energized and the time delay relay is ready to accept another trigger. FLASHER(Off First) Upon application of input voltage, the time delay (t) begins. At the end of the time delay (t), the output is energized and remains in that condition for the time delay (t). At the end of the time delay (t), the output is de-energized and the sequence repeats until input voltage is removed. FLASHER(On First) Upon application of input voltage, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized and remains in that condition for the time delay (t). At the end of the time delay (t), the output is energized and the sequence repeats until input voltage is removed. ON/OFF DELAY Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the time delay (t1) begins. At the end of the time delay (t1), the output is energized. When the trigger is removed, the output contacts remain energized for the time delay (t2). At the end of the time delay (t2), the output is de-energized & the time delay relay is ready to accept another trigger. If the trigger is removed during time delay period (t1), the output will remain de-energized and time delay (t1) will reset. If the trigger is re-applied during time delay period (t2), the output will remain energized and the time delay (t2) will reset. SINGLE SHOTFALLING EDGE Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output remains de-energized. Upon removal of the trigger, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized unless the trigger is removed and re-applied prior to time out (before time delay (t) elapses). Continuous cycling of the trigger at a rate faster than the time delay (t) will cause the output to remain energized indefinitely.
WATCHDOG Retriggerable Single Shot Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized unless the trigger is removed and re-applied prior to time out (before time delay (t) elapses). Continuous cycling of the trigger at a rate faster than the time delay (t) will cause the output to remain energized indefinitely. TRIGGERED ON DELAY Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the time delay (t) begins. At the end of the time delay (t), the output is energized and remains in that condition as long as both the trigger and control voltage remains. If the trigger is removed during the time delay (t), the output remains de-energized & the time delay (t) is reset.
REPEAT CYCLE(OFF 1st) Upon application of input voltage, the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of this time delay, the output is de-energized and the sequence repeats until input voltage is removed. REPEAT CYCLE(ON 1st) Upon application of input voltage, the output is energized and the time delay (t1) begins. At the end of the time delay (t1), the output is de-energized and remains in that condition for the time delay (t2). At the end of this time delay, the output is energized and the sequence repeats until input voltage is removed.
DELAYED INTERVAL Single Cycle Upon application of input voltage, the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of this time delay (t2), the output is de-energized. Input voltage must be removed to reset the time delay relay.
TRIGGERED DELAYED INTERVAL Single Cycle Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of the time delay (t2), the output is de-energized & the relay is ready to accept another trigger. During both time delay (t1) & time delay (t2), the trigger is ignored. TRUE OFF DELAY Upon application of input voltage, the output is energized. When the input voltage is removed, the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Input voltage must be applied for a minimum of 0.5 seconds to assure proper operation. Any application of the input voltage during the time delay (t) will reset the time delay. No external trigger is required.
ON DELAY/ TRUE OFF DELAY Upon application of input voltage, the time delay (t1) begins. At the end of the time delay (t1), the output is energized. When the input voltage is removed, the output remains energized for the time delay (t2). At the end of the time delay (t2), the output is de-energized. Input voltage must be applied for a minimum of 0.5 seconds to assure proper operation. Any application of the input voltage during the time delay (t2) will keep the output energized & reset the time delay (t2). No external trigger is required. SINGLE SHOT-FLASHER Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the time delay (t1) begins and the output is energized for the time delay (t2). At the end of this time delay (t2), the output is de-energized and remains in that condition for the time delay (t2). At the end of the time delay (t2), the output is energized and the sequence repeats until time delay (t1) is completed. During the time delay (t1), the trigger is ignored. ON DELAY-FLASHER Upon application of input voltage, the time delay begins (t1). At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of this time delay (t2), the output is de-energized and remains in that condition for the time delay (t2). At the end of the time delay (t2), the output is energized and the sequence repeats until input voltage is removed.
PERCENTAGE Upon initial application of input voltage, the output is energized and time delay (t1) begins. Time Delay (t1) is adjustable as a percentage of the overall cycle time (t2). At the end of time delay (t1), the output is de-energized for the remainder of overall cycle (t2-t1). The sequence then repeats until input voltage is removed. If input voltage is removed and reapplied, the timing cycle will continue from where it left off when the input voltage was removed. A setting of 100% energizes the output continuously while a setting of 0% de-energizes the output continuously.
PERCENTAGE (NO MEMORY) Upon initial application of input voltage, the output is energized and time delay (t1) begins. Time Delay (t1) is adjustable as a percentage if the overall cycle time (t2). At the end of time delay (t1), the output is de-energized for the remainder of overall cycle (t2-t1). The sequence then repeats until input voltage is removed. If input voltage is removed and reapplied, the timing cycle will be reset. A setting of 100% energizes the output continuously while a setting of 0% de-energizes the output continuously.
|
|
Recent Posts
How to use Gateway Convertors Wednesday, March 10, 2021
Voltage Monitor Relays Wednesday, December 9, 2020
Why do you need a transformer ? Wednesday, June 10, 2020
Relays vs. Solenoids vs. Contactors: A Comparison Thursday, June 4, 2020
ABB Opens new distribution center in Phoenix! Thursday, May 28, 2020
Search Posts |
|
Blog Categories
General
12/09/2020 - Voltage Monitor Relays
02/13/2019 - 5 Benefits of Industrial Ether
02/06/2019 - Remarkable Benefits of Liquid
01/30/2019 - Electrical Protection of Induc
01/16/2019 - 5 Causes of Motor Failure and
01/02/2019 - Everything You Need to Know Ab
12/28/2018 - Different Types of Soft Starte
12/12/2018 - Different Types of Programmabl
12/05/2018 - Variable Frequency Drive
11/30/2018 - Applications of Programmable L
11/14/2018 - The Importance of Relays
11/07/2018 - Everything You Need to Know Ab
07/27/2018 - What Are Unearthed Outlets & W
07/11/2018 - The Difference between a Light
07/02/2018 - How Can I Stop My Smoke Detect
06/29/2018 - Understanding Operator Interfa
06/13/2018 - The Importance of Brand Authen
06/04/2018 - Stepper Motors for Machine Aut
04/16/2018 - The Use of Soft Starters and I
04/02/2018 - The Types & Advantages of Usin
03/27/2018 - The New Designs of Contact Blo
03/27/2018 - Important Things You Need to K
03/14/2018 - Limit Switches Improve Safety
03/05/2018 - Soft Starters- Advantages, Typ
02/27/2018 - 8 Reasons to Use a Fuse
02/16/2018 - 4 Benefits of Programmable Log
02/06/2018 - 3 Reasons Why Circuit Breakers
01/29/2018 - 2 Gas Based Generators You Did
01/18/2018 - Common Types of Generators You
01/05/2018 - 3 Machine Safety Measures That
Enclosures
02/23/2019 - Different Types of Electrical
10/31/2018 - The importance of installing e
08/06/2018 - Metal or Plastic? How About Ne
Circuit Protection
09/12/2018 - Why Are Fuses Important?
08/31/2018 - Miniature Circuit Breakers: Ty
08/15/2018 - Miniature Circuit Breakers: Ty
05/30/2018 - How to Replace a Fuse
05/21/2018 - Circuit Breaker vs. Fuse: Whic
05/07/2018 - All You Need to Know About Cir
04/02/2018 - 5 Reasons Why Circuit Breakers
01/01/2018 - ABB Terminal Blocks Are Child’
01/25/2016 - Why Do You Want Miniature Circ
01/12/2016 - Lovato Now At Midwest Equipmen
Machine Safety
Midwest Enclosures
ABB New Facility
Relays vs. Solenoids vs. Contactors: A Comparison
Transformers
Gateway Convertors
New Mersen Product !
Supply Chain Shortages
Why is Motor Control Important ?
What Do Time Switches Do?
Understanding Time Delay Relay Functions
Using Liquid Level Control Relays
Intrinsically Safe Relays
|
Subscribe To Our Blog |
|